Battery Capacity from Runtime Calculator

Load watts + desired runtime hours + battery voltage → required battery capacity in Ah and Wh (with safety margin).

Inputs

Result

Required battery capacity
88.9 Ah @ 12 V
1,066.7 Wh · 50% DoD, η=0.9
  • Load60 W
  • Runtime8 h
  • Battery voltage12 V
  • Usable DoD50%
  • Conversion η90%
  • Energy delivered480.0 Wh
  • Required battery energy1,066.7 Wh
  • Required capacity88.89 Ah
  • Naive (no margin)40.00 Ah

Step-by-step

  1. Energy delivered to load = 60 W × 8 h = 480.00 Wh.
  2. Energy battery must store = Wh / (DoD · η) = 480.00 / (0.5 · 0.9) = 1,066.67 Wh.
  3. Capacity in Ah = Wh / V = 1,066.67 / 12 = 88.89 Ah.

How to use this calculator

  • Enter the constant load wattage.
  • Enter target runtime in hours.
  • Pick battery voltage (12 V, 24 V, 48 V common).
  • Pick usable DoD based on chemistry.
  • Set inverter / DC-DC efficiency (0.90 typical).

About this calculator

Battery sizing from a runtime target is straightforward energy bookkeeping: Wh required = load (W) × runtime (h), inflated by usable depth of discharge and converter efficiency. The DoD adjustment matters because lead-acid loses cycle life when discharged below 50%; lithium-iron-phosphate (LFP) tolerates 80%+; only some lithium-ion chemistries handle 100% safely. The η factor covers inverter losses (for AC loads) or DC-DC converter losses (for buck/boost). Peukert's law adds a small correction for very high discharge rates but is usually negligible at consumer scales.

What this calculator does

This calculator answers: "I want to power a W-watt load for H hours from a battery at V volts — how much capacity do I need?" It accounts for the two real-world inflation factors that take the naive Wh = W × h answer and turn it into a usable battery spec: usable depth of discharge (a function of chemistry) and converter / inverter efficiency. The output is in both Wh and Ah so you can compare against any battery datasheet.

How it works — the formula

Wh_load = P · t Wh_battery = Wh_load / (DoD · η) Ah_battery = Wh_battery / V

Power times time is energy delivered. To deliver that much, the battery must store more — divided by the depth-of-discharge fraction (so it never goes below the safe-discharge floor) and divided again by the converter / inverter efficiency. Divide by nominal voltage to convert Wh to Ah.

Sources: Battery University — Sizing and Application (typical DoD, Peukert) · IEEE Std 1188-2005 — Recommended Practice for Maintenance, Testing, and Replacement of Valve-Regulated Lead-Acid (VRLA) Batteries · US DOE — Energy Storage Handbook (Wh / Ah / DoD conventions)

Worked examples

Example 1
60 W LED for 8 h on a 12 V LFP
Inputs:
P=60, t=8, V=12, DoD=0.8, η=0.90
Output:
Wh_battery ≈ 667 Wh; Ah_battery ≈ 55.6 Ah

A 100 Ah LFP would have ample margin.

Example 2
1500 W appliance for 1 h on lead-acid
Inputs:
P=1500, t=1, V=12, DoD=0.5, η=0.85
Output:
Wh ≈ 3529; Ah ≈ 294

Lead-acid users need much larger banks than lithium for the same usable energy.

Example 3
Solar inverter 200 W for 4 h, 48 V LFP
Inputs:
P=200, t=4, V=48, DoD=0.8, η=0.92
Output:
Wh ≈ 1087; Ah ≈ 22.6

Higher-voltage banks need less Ah for the same energy — saves on conductor cost.

When to use this vs other tools

Use this for discharge-side sizing. For full off-grid systems you also need panel sizing and days of autonomy.

  • Battery Series/Parallel

    Use to figure out how many cells in series and parallel to build a pack of the required voltage and capacity.

  • kWh Cost per Month

    Use to compare battery payback against just buying power from the grid.

  • Voltage Drop

    Use to size the conductors between battery and load — long DC runs can lose significant power.

Authority note

IEEE 1188 / Battery University

The Wh/Ah/DoD conventions used here are standard across the battery industry. IEEE 1188 codifies the practice; Battery University is the most-cited practitioner reference.

Limitations

  • Assumes constant load. Variable loads (motors with inrush, refrigerators with cycling compressors) need higher peak-current ratings.
  • No Peukert correction — accurate within ~5% at discharge rates ≤ 0.5C, conservative above that.
  • Temperature: lead-acid loses ~1% capacity per °C below 25 °C; lithium loses much less but throttles at low temperature.
  • Aging: lead-acid loses ~20% at end-of-life; lithium ~20% by cycle count rather than years. Oversize for replacement intervals.

Critical loads (medical, life-safety) require redundancy beyond simple sizing. Consult a licensed electrical engineer for code-compliant standby-power design.

Frequently asked

That gives the energy delivered, not the capacity you need to install. Real batteries should not be fully discharged and converters lose 10-20% — the DoD and η factors capture both.

Related calculators

More tools you might like